Fire Alarm Battery Capacity Calculator
NFPA 72 ยท Fire Alarm Systems
Project record
- Project ID
- Not entered
- Area
- Not entered
- System
- Not entered
- Revision
- Not entered
- Prepared by
- Not entered
- Checked by
- Not entered
Inputs
- Standby current
- 300 mA
- Standby duration
- 24 hr
- Alarm current
- 1800 mA
- Alarm duration
- 5 min
- Apply 20% aging margin
- Yes
Results
- Required capacity
- 7.35 AH
- Final capacity
- 8.82 AH
- Suggested battery
- 12 AH
Calculation basis
- Formula
- AH = standby current x hours + alarm current x alarm hours
- Reference standard
- NFPA 72
- Professional boundary
- Verify adopted code, project criteria, listed equipment data, and AHJ requirements before relying on this record.