Authority workflow
Fire Protection Submittal Checklist
A submittal readiness workflow for keeping drawings, calculations, device data, water supply records, and AHJ notes organized before review.
Priority
3
Authority inputs
Checklist
4
Review checks
Source refs
4
Official/source-class entries
Source priority
Record the source that controls the project before relying on worksheet or calculator output.
| Source | Use | Record |
|---|---|---|
| Permit application requirements | Identify required submittal documents and review format. | Permit checklist and jurisdiction instructions. |
| Project specifications | Capture owner, insurer, and engineer requirements beyond baseline code. | Specification section and submittal matrix. |
| AHJ comments | Close review comments before resubmittal. | Comment response log and revised sheet/calculation reference. |
Source directory
Official entry points and source classes used to verify the authority record. These links do not replace state, local, or AHJ confirmation.
| Source | Class | Use | Limit | Checked |
|---|---|---|---|---|
| Local AHJ, building department, or fire prevention bureau | Jurisdiction source class | Primary verification source for local amendments, permit path, and approval expectations. | Requires project address or jurisdiction; local amendments can override generic assumptions. | 2026-06-19 |
| NFPA 13 standard page | Official NFPA standard entry | Official NFPA entry point for the sprinkler system installation standard. | Do not copy standard text; use only as an official source link and edition-basis record. | 2026-06-19 |
| NFPA 72 standard page | Official NFPA standard entry | Official NFPA entry point for fire alarm and signaling code context. | Do not copy standard text; use only as an official source link and edition-basis record. | 2026-06-19 |
| Project specifications, owner criteria, insurer, and listings | Project source class | Captures requirements that may exceed adopted code or baseline calculator assumptions. | Project-specific; cannot be generalized across all users or states. | 2026-06-19 |
Checklist
Use this as a workpaper checklist before submittal, AHJ coordination, or final design reliance.
| Item | Evidence | Owner |
|---|---|---|
| Drawings match calculation assumptions | Sheet index, revision, design area, circuit, or riser reference | Designer |
| Calculation worksheets included | Hydraulic, battery, water supply, pump, or hazard worksheet output | Engineer or contractor |
| Product data supports inputs | Sprinkler listing, device current sheet, pump curve, or panel data | Submittal coordinator |
| AHJ notes resolved | Response matrix and revised document reference | Project lead |
Form fields
Fields to retain in the project record or worksheet notes.
| Field | Purpose | Required |
|---|---|---|
| Submittal package ID | Connects documents, calculations, and revisions. | Required |
| Drawing revision | Prevents calculations from being reviewed against stale drawings. | Required |
| Calculation worksheet links | Identifies supporting worksheet records. | Required |
| Product data basis | Shows that listed data supports typed inputs. | Required |
| Open comments | Keeps unresolved AHJ or reviewer issues visible. | Conditional |
Project record worksheet
Use these record sections to keep project identity, workflow inputs, source evidence, and closeout status together.
Project identity
Tie the authority record to one project, jurisdiction, system, and review date.
| Field | Record to keep | Required | Evidence |
|---|---|---|---|
| Project name | Project identifier used on drawings, calculations, and submittal logs. | Required | Project title block or permit application |
| Project address | Street address or campus/location identifier for jurisdiction routing. | Required | Permit application, drawing title block, or owner record |
| Jurisdiction | State, city, county, fire district, or other enforcing jurisdiction. | Required | Permit application or AHJ directory |
| System scope | Sprinkler, fire alarm, water supply, pump, inspection/testing, or mixed scope. | Required | Drawing scope, test report, or worksheet name |
| Record date | Date this authority record was prepared or last reviewed. | Required | Record issue date |
Submittal package record
Confirm drawings, calculations, product data, and AHJ comments are aligned before submittal or resubmittal.
| Field | Record to keep | Required | Evidence |
|---|---|---|---|
| Package ID and issue date | Submittal package name, issue date, and resubmittal number if applicable. | Required | Submittal transmittal or document control log |
| Drawing revision basis | Sheet index, revision date, and system area covered by the calculation. | Required | Drawing title block and sheet index |
| Calculation attachments | Worksheet outputs, calculator results, hydraulic calculations, battery calculations, or water supply records included. | Required | Calculation package table of contents |
| Product data match | Sprinkler listing, device current sheet, pump curve, panel data, or listing basis supporting inputs. | Required | Manufacturer product data and listing sheets |
| Open AHJ/reviewer comments | Unresolved comments, responsible owner, and next action. | Conditional | Comment response matrix |
Source evidence
Retain the source trail used to support the authority decision without publishing unsupported legal conclusions.
| Field | Record to keep | Required | Evidence |
|---|---|---|---|
| Permit application requirements | Permit checklist and jurisdiction instructions. | Required | Identify required submittal documents and review format. |
| Project specifications | Specification section and submittal matrix. | Required | Capture owner, insurer, and engineer requirements beyond baseline code. |
| AHJ comments | Comment response log and revised sheet/calculation reference. | Required | Close review comments before resubmittal. |
Review closeout
Record the pass/fail status of each stop point before moving calculator or worksheet output forward.
| Field | Record to keep | Required | Evidence |
|---|---|---|---|
| Document match | Drawings, calculations, and product data reference the same system and revision. | Required | Hold submittal package for coordination. |
| Calculation traceability | Each calculation result links back to input source and worksheet gate. | Required | Return to worksheet before submittal. |
| Comment closure | AHJ comments are answered or assigned. | Required | Do not mark package ready. |
Closeout records
Keep these items with the project file before treating the authority workflow as complete.
| Record | Status |
|---|---|
| Submittal checklist record issue date and reviewer. | Retain with project file |
| Source links or source-class notes used for the project decision. | Retain with project file |
| Open AHJ, local amendment, or project-specification conflicts. | Retain with project file |
| Related worksheet, calculator, reference, or standard hub used after this authority record. | Retain with project file |
Acceptance gates
Stop points that prevent calculator output from being treated as final without authority context.
| Gate | Pass condition | Fail action |
|---|---|---|
| Document match | Drawings, calculations, and product data reference the same system and revision. | Hold submittal package for coordination. |
| Calculation traceability | Each calculation result links back to input source and worksheet gate. | Return to worksheet before submittal. |
| Comment closure | AHJ comments are answered or assigned. | Do not mark package ready. |
Workflow handoffs
Open the project workflow after the authority record is documented.
| Type | Linked workflow | Open |
|---|---|---|
| Worksheet | NFPA 13 Hydraulic Design Worksheet | Open |
| Worksheet | Fire Alarm Battery and NAC Worksheet | Open |
| Worksheet | Fire Pump Selection Worksheet | Open |
| Reference | US Code Adoption and AHJ Checkpoints | Open |
| Reference | Fire Sprinkler K-Factor Table | Open |
| Reference | AWG Wire Resistance Table for Fire Alarm Circuits | Open |
| Standard hub | NFPA 13 Sprinkler System Calculators | Open |
| Standard hub | NFPA 72 Fire Alarm Calculators | Open |