NFPA in USA

Authority workflow

NFPA 13, 72, and 25 Edition Basis Worksheet

A worksheet for recording which NFPA 13, NFPA 72, and NFPA 25 editions apply by adoption, contract, listing, owner criteria, or AHJ direction.

NFPA edition basis worksheet4 checks5 form fields

Priority

3

Authority inputs

Checklist

4

Review checks

Source refs

6

Official/source-class entries

Source priority

Record the source that controls the project before relying on worksheet or calculator output.

SourceUseRecord
Adopted code textIdentify referenced NFPA edition for enforceable requirements.Code section and referenced edition.
Project specificationsIdentify contract-required standards and stricter project criteria.Specification section and issue date.
AHJ directionResolve conflicts between adopted code, current edition, and project requirements.AHJ response and date.

Source directory

Official entry points and source classes used to verify the authority record. These links do not replace state, local, or AHJ confirmation.

SourceClassUseLimitChecked
NFPA 13 standard page Official NFPA standard entryOfficial NFPA entry point for the sprinkler system installation standard.Do not copy standard text; use only as an official source link and edition-basis record.2026-06-19
NFPA 72 standard page Official NFPA standard entryOfficial NFPA entry point for fire alarm and signaling code context.Do not copy standard text; use only as an official source link and edition-basis record.2026-06-19
NFPA 25 standard page Official NFPA standard entryOfficial NFPA entry point for inspection, testing, and maintenance edition-basis context.Do not copy standard text; use only as an official source link and edition-basis record.2026-06-19
State code agency or state fire marshalJurisdiction source classPrimary verification source for adopted state building or fire code edition.Requires project state; this site must not infer the answer without a cited state source.2026-06-19
Local AHJ, building department, or fire prevention bureauJurisdiction source classPrimary verification source for local amendments, permit path, and approval expectations.Requires project address or jurisdiction; local amendments can override generic assumptions.2026-06-19
Project specifications, owner criteria, insurer, and listingsProject source classCaptures requirements that may exceed adopted code or baseline calculator assumptions.Project-specific; cannot be generalized across all users or states.2026-06-19

Checklist

Use this as a workpaper checklist before submittal, AHJ coordination, or final design reliance.

ItemEvidenceOwner
NFPA 13 basis recordedAdopted edition, specification, or AHJ noteSprinkler designer
NFPA 72 basis recordedAdopted edition, specification, or AHJ noteFire alarm designer
NFPA 25 basis recordedAdopted edition, owner program, or AHJ noteITM provider
Edition conflict resolvedDecision note where adopted, current, and specified editions differEngineer of record

Form fields

Fields to retain in the project record or worksheet notes.

FieldPurposeRequired
StandardIdentifies NFPA 13, NFPA 72, NFPA 25, or another referenced standard.Required
Edition yearRecords the edition used for worksheet assumptions.Required
Basis typeDistinguishes adopted code, specification, listing, owner requirement, or AHJ direction.Required
Source noteCaptures the source section, document, or contact.Required
Conflict noteExplains edition differences or unresolved interpretation.Conditional

Project record worksheet

Use these record sections to keep project identity, workflow inputs, source evidence, and closeout status together.

Project identity

Tie the authority record to one project, jurisdiction, system, and review date.

FieldRecord to keepRequiredEvidence
Project nameProject identifier used on drawings, calculations, and submittal logs.RequiredProject title block or permit application
Project addressStreet address or campus/location identifier for jurisdiction routing.RequiredPermit application, drawing title block, or owner record
JurisdictionState, city, county, fire district, or other enforcing jurisdiction.RequiredPermit application or AHJ directory
System scopeSprinkler, fire alarm, water supply, pump, inspection/testing, or mixed scope.RequiredDrawing scope, test report, or worksheet name
Record dateDate this authority record was prepared or last reviewed.RequiredRecord issue date

NFPA edition basis record

Document the edition basis for each applicable NFPA standard before final worksheet reliance.

FieldRecord to keepRequiredEvidence
NFPA 13 edition basisEdition year and basis type for sprinkler design assumptions.RequiredAdopted code reference, specification, listing, or AHJ direction
NFPA 72 edition basisEdition year and basis type for fire alarm and signaling assumptions.RequiredAdopted code reference, specification, listing, or AHJ direction
NFPA 25 edition basisEdition year and basis type for inspection, testing, and maintenance records.RequiredAdopted code reference, facility program, contract, or AHJ direction
Edition conflict noteDifference between adopted edition, current edition, project specification, listing, or AHJ direction.ConditionalDecision log or AHJ question response
Stop gate statusWhether edition basis is verified, pending AHJ response, or unknown.RequiredAuthority record closeout note

Source evidence

Retain the source trail used to support the authority decision without publishing unsupported legal conclusions.

FieldRecord to keepRequiredEvidence
Adopted code textCode section and referenced edition.RequiredIdentify referenced NFPA edition for enforceable requirements.
Project specificationsSpecification section and issue date.RequiredIdentify contract-required standards and stricter project criteria.
AHJ directionAHJ response and date.RequiredResolve conflicts between adopted code, current edition, and project requirements.

Review closeout

Record the pass/fail status of each stop point before moving calculator or worksheet output forward.

FieldRecord to keepRequiredEvidence
Edition traceabilityEach applicable NFPA edition has a source and basis type.RequiredHold worksheet output as preliminary.
Conflict reviewEdition conflicts are resolved or assigned to AHJ/project lead.RequiredEscalate before submittal.
Tool alignmentCalculator assumptions and worksheet QA gates reference the same edition basis.RequiredRevise worksheet inputs before relying on results.

Closeout records

Keep these items with the project file before treating the authority workflow as complete.

RecordStatus
Edition basis record issue date and reviewer.Retain with project file
Source links or source-class notes used for the project decision.Retain with project file
Open AHJ, local amendment, or project-specification conflicts.Retain with project file
Related worksheet, calculator, reference, or standard hub used after this authority record.Retain with project file

Acceptance gates

Stop points that prevent calculator output from being treated as final without authority context.

GatePass conditionFail action
Edition traceabilityEach applicable NFPA edition has a source and basis type.Hold worksheet output as preliminary.
Conflict reviewEdition conflicts are resolved or assigned to AHJ/project lead.Escalate before submittal.
Tool alignmentCalculator assumptions and worksheet QA gates reference the same edition basis.Revise worksheet inputs before relying on results.

Workflow handoffs

Open the project workflow after the authority record is documented.

TypeLinked workflowOpen
WorksheetNFPA 13 Hydraulic Design WorksheetOpen
WorksheetFire Alarm Battery and NAC WorksheetOpen
WorksheetHydrant Flow and Water Supply WorksheetOpen
ReferenceUS Code Adoption and AHJ CheckpointsOpen
Standard hubNFPA 13 Sprinkler System CalculatorsOpen
Standard hubNFPA 72 Fire Alarm CalculatorsOpen
Standard hubNFPA 25 Flow Test and Water Supply CalculatorsOpen
Engineering disclaimer
NFPA in USA provides engineering workpapers, calculation checks, and reference tables for project screening and coordination. Final design decisions, code interpretations, submittals, and acceptance records must be completed by qualified professionals and verified against the adopted code, project criteria, listings, and Authority Having Jurisdiction requirements. This site does not issue signed or sealed engineering documents.

FAQ

What is the NFPA edition basis workflow for?+
It keeps jurisdiction, AHJ, adopted edition, submittal, and inspection records visible before calculator or worksheet results are used on a project.
Does this replace the AHJ or adopted code?+
No. It is a project record workflow. Always verify adopted codes, local amendments, required editions, and approval requirements with the applicable Authority Having Jurisdiction.
Why is this separate from a calculator?+
A calculator produces a number. Authority records explain whether that number is being used under the correct jurisdiction, standard edition, review path, and project criteria.