NFPA in USA

NFPA 72 calculator

Fire Alarm NAC Voltage Drop Calculator

Calculate round-trip voltage drop and end-of-line voltage for notification appliance and signaling circuits.

Fire Alarm SystemsNFPA 72Workpaper

Calculation workpaper

Enter inputs, review outputs, then use the guidance below before carrying the result forward.

US customary units

Calculation inputs

Enter project screening values in the units shown.

Ready

Worksheet header

Optional project fields for keeping the calculation screen traceable.

Results

Ready

Conductor resistance

6.385 ohm/1000 ft

Calculated output

Round-trip length

600 ft

Calculated output

Total circuit resistance

3.831 ohm

Calculated output

Wire size18 AWG
Conductor resistance6.385ohm/1000 ft
Round-trip length600ft
Total circuit resistance3.831ohm
Voltage drop5.75V
End-of-line voltage18.25V
Voltage screenPass

Calculation basis

Use the formula and linked reference data after the result is visible. Keep input selection separate from the calculation screen.

Formula

Vdrop = I x R x 2L / 1000

Copper Wire Resistance

Wire SizeOhms per 1000 ft
12 AWG1.588
14 AWG2.525
16 AWG4.016
18 AWG6.385
20 AWG10.15
22 AWG16.14

Use this result

Use end-of-line voltage to decide whether the circuit needs larger wire, shorter length, or lower load.

Check before use
Confirm one-way route length, conductor size, current, source voltage, and listed minimum voltage.
Common pitfall
Entering round-trip length as one-way length doubles the voltage drop.

Input evidence

Confirm these values before using the result.

  • Wire size
  • Circuit current (A)
  • One-way circuit length (ft)
  • Source voltage (V)
  • Minimum device voltage (V)

Authority basis

Check jurisdiction, AHJ, submittal, and edition records before using this result as project evidence.

Record retention

Save the PDF after project fields, inputs, and results are set.

PDF includes

  • Project header and calculator inputs
  • Computed result rows and warnings
  • Formula, reference basis, and professional boundary

Check before filing

  • Input traceability
  • Method review
  • Output reasonableness
  • Professional boundary
Engineering disclaimer
NFPA in USA provides engineering workpapers, calculation checks, and reference tables for project screening and coordination. Final design decisions, code interpretations, submittals, and acceptance records must be completed by qualified professionals and verified against the adopted code, project criteria, listings, and Authority Having Jurisdiction requirements. This site does not issue signed or sealed engineering documents.

FAQ

What is this Fire Alarm NAC Voltage Drop calculator for?+
Use it to compute a defined fire protection value from documented inputs, then retain the inputs, result, formula, and warnings with the project record.
Are the results suitable for permit submission?+
Use the saved record only after it is checked against adopted code, project criteria, equipment listings, and AHJ requirements.