Velocity Pressure Calculator

Calculate sprinkler pipe velocity pressure from flow and internal diameter.

Sprinkler SystemsNFPA 13Workpaper

Calculation workpaper

Enter inputs, review outputs, then use the guidance below before carrying the result forward.

US customary units

Calculation inputs

Enter project screening values in the units shown.

Ready

Worksheet header

Optional project fields for keeping the calculation screen traceable.

Results

Ready

Internal diameter

3.068 in

Calculated output

Velocity pressure

0.79 psi

Calculated output

Nominal pipe size3"
Pipe scheduleSchedule 40
Internal diameter3.068in
Velocity pressure0.79psi

Before project use

Save the input source, formula, units, warnings, and result with the project record before carrying this screening value into design coordination or AHJ review.

Next calculator: Sprinkler Pipe Velocity Calculator

Calculation basis

Use the formula and linked reference data after the result is visible. Keep input selection separate from the calculation screen.

Formula

Pv = 0.001123 x Q^2 / d^4

Nominal Pipe Diameter

Nominal SizeSchedule 10 ID (in)Schedule 40 ID (in)
3/4"0.8840.824
1"1.0971.049
1-1/4"1.4421.38
1-1/2"1.6821.61
2"2.1572.067
2-1/2"2.6352.469

Professional review path

Use this calculator as a workpaper step: collect evidence, make a review decision, then move the record into the next workflow.

Evidence to collect
  • Flow assigned to the pipe segment or hydraulic point being checked.
  • Nominal pipe size and schedule used for internal diameter.
  • Hydraulic review note explaining why velocity pressure is being retained.
Review decision
Decide whether velocity pressure should be kept as supporting hydraulic evidence before completing friction-loss or demand review.

Use this result

Use velocity pressure as a hydraulic screening value for the selected pipe condition.

Check before use
Confirm flow and internal diameter are from the same pipe segment.
Common pitfall
Using velocity pressure without friction loss omits the controlling pipe-run pressure drop.

Input evidence

Confirm these values before using the result.

  • Flow rate (GPM)
  • Nominal pipe size
  • Pipe schedule

Authority basis

Check jurisdiction, AHJ, submittal, and edition records before using this result as project evidence.

Record retention

Save the PDF after project fields, inputs, and results are set.

PDF includes

  • Project header and calculator inputs
  • Computed result rows and warnings
  • Formula, reference basis, and professional boundary

Check before filing

  • Input traceability
  • Method review
  • Output reasonableness
  • Professional boundary
Engineering disclaimer
NFPA in USA provides engineering workpapers, calculation checks, and reference tables for project screening and coordination. Final design decisions, code interpretations, submittals, and acceptance records must be completed by qualified professionals and verified against the adopted code, project criteria, listings, and Authority Having Jurisdiction requirements. This site does not issue signed or sealed engineering documents.

FAQ

What is this Velocity Pressure calculator for?+
Use it to compute a defined fire protection value from documented inputs, then retain the inputs, result, formula, and warnings with the project record.
Are the results suitable for permit submission?+
Use the saved record only after it is checked against adopted code, project criteria, equipment listings, and AHJ requirements.