NFPA in USA calculation workpaper
Pipe Velocity Calculator
NFPA 13 ยท Sprinkler Systems
Project record
- Project ID
- Not entered
- Area
- Not entered
- System
- Not entered
- Revision
- Not entered
- Prepared by
- Not entered
- Checked by
- Not entered
Inputs
- Flow rate
- 250 GPM
- Nominal pipe size
- 3"
- Pipe schedule
- Schedule 40
Results
- Nominal pipe size
- 3"
- Pipe schedule
- Schedule 40
- Internal diameter
- 3.068 in
- Target velocity
- 20 ft/s
- Velocity within target
- Pass
- Pipe velocity
- 10.85 ft/s
Calculation basis
- Formula
- v = Q / (2.448 x d^2)
- Reference standard
- NFPA 13
- Professional boundary
- Verify adopted code, project criteria, listed equipment data, and AHJ requirements before relying on this record.