NFPA in USA calculation workpaper
Fire Pump Sizing Calculator
NFPA 13 ยท Sprinkler Systems
Project record
- Project ID
- Not entered
- Area
- Not entered
- System
- Not entered
- Revision
- Not entered
- Prepared by
- Not entered
- Checked by
- Not entered
Inputs
- Sprinkler demand
- 500 GPM
- Hose allowance
- 250 GPM
- Required system pressure
- 90 psi
- Elevation above supply
- 20 ft
Results
- Sprinkler demand
- 500 GPM
- Hose allowance
- 250 GPM
- Rated flow screen
- 750 GPM
- Discharge pressure screen
- 98.66 psi
- Elevation pressure
- 8.66 psi
Calculation basis
- Formula
- Pump demand = sprinkler demand + hose allowance
- Reference standard
- NFPA 13
- Professional boundary
- Verify adopted code, project criteria, listed equipment data, and AHJ requirements before relying on this record.