Estimate required fire pump rated flow and discharge pressure for sprinkler demand screening.

Fire PumpEngineeringWorkpaper

Calculation workpaper

Enter inputs, review outputs, then use the guidance below before carrying the result forward.

US customary units

Calculation inputs

Enter project screening values in the units shown.

Ready

Worksheet header

Optional project fields for keeping the calculation screen traceable.

Results

Ready

Sprinkler demand

500 GPM

Calculated output

Hose allowance

250 GPM

Calculated output

Rated flow screen

750 GPM

Calculated output

Sprinkler demand500GPM
Hose allowance250GPM
Rated flow screen750GPM
Discharge pressure screen98.66psi
Elevation pressure8.66psi

Calculation basis

Use the formula and linked reference data after the result is visible. Keep input selection separate from the calculation screen.

Formula

Pump size based on system flow and pressure demand

Review note

Confirm units before comparing results. If the value controls a design choice, check it against adopted criteria and project-specific inputs.

Use this result

Use rated flow and pressure screen to begin pump selection coordination.

Check before use
Confirm demand, hose allowance, pressure, and elevation before comparing to pump options.
Common pitfall
Pump sizing without water supply review can miss suction or available pressure limitations.

Input evidence

Confirm these values before using the result.

  • Sprinkler demand (GPM)
  • Hose allowance (GPM)
  • Required system pressure (psi)
  • Elevation (ft)

Authority basis

Check jurisdiction, AHJ, submittal, and edition records before using this result as project evidence.

Record retention

Save the PDF after project fields, inputs, and results are set.

PDF includes

  • Project header and calculator inputs
  • Computed result rows and warnings
  • Formula, reference basis, and professional boundary

Check before filing

  • Input traceability
  • Method review
  • Output reasonableness
  • Professional boundary
Engineering disclaimer
NFPA in USA provides engineering workpapers, calculation checks, and reference tables for project screening and coordination. Final design decisions, code interpretations, submittals, and acceptance records must be completed by qualified professionals and verified against the adopted code, project criteria, listings, and Authority Having Jurisdiction requirements. This site does not issue signed or sealed engineering documents.

FAQ

What is this Fire Pump Sizing calculator for?+
Use it to compute a defined fire protection value from documented inputs, then retain the inputs, result, formula, and warnings with the project record.
Are the results suitable for permit submission?+
Use the saved record only after it is checked against adopted code, project criteria, equipment listings, and AHJ requirements.