NFPA 72 work procedure
NFPA 72 Battery Sizing Workflow
A practical calculation sequence for standby load, alarm load, aging margin, and standard battery size selection.
Guide workflow
Follow the sequence as an engineering workflow: each phase lists the action, tools, and evidence to retain before moving forward.
| Phase | Action | Tools | Evidence to keep |
|---|---|---|---|
| Step 1 | Collect total standby current for all connected equipment. | Fire Alarm Battery Capacity Calculator | Document the source used to start the NFPA 72 workflow. |
| Step 2 | Collect total alarm current for notification and control loads. | Fire Alarm Battery Capacity Calculator, Fire Alarm NAC Voltage Drop Calculator | Keep calculation notes showing how this step supports: collect total alarm current for notification and control loads. |
| Step 3 | Apply the required standby and alarm durations. | Fire Alarm Battery Capacity Calculator, Fire Alarm NAC Voltage Drop Calculator | Keep calculation notes showing how this step supports: apply the required standby and alarm durations. |
| Step 4 | Apply the aging margin when required by the project basis. | Fire Alarm Battery Capacity Calculator, Fire Alarm NAC Voltage Drop Calculator | Keep calculation notes showing how this step supports: apply the aging margin when required by the project basis. |
| Step 5 | Select the next standard battery size and verify cabinet constraints. | Fire Alarm Battery Capacity Calculator, Fire Alarm NAC Voltage Drop Calculator | Record the reviewed output, warning state, and next review decision. |
Required records
- 1NFPA 72 workflow basis and project condition that triggered this guide.
- 2Input source notes for each calculator used in the sequence.
- 3Intermediate results, warnings, and pass/fail states from linked tools.
- 4Final review notes for engineering review, submittal review, field check, or AHJ coordination.
Review gates
- 1The sequence starts with project-specific inputs, not untouched default values.
- 2Each intermediate result is checked before being transferred into the next calculator.
- 3Warnings or failed screens are resolved or documented before final project use.
- 4NFPA 72 context and local AHJ requirements remain part of the final review.
Next-step notes
- 1Use this guide as a workflow checklist, not as a sealed design package.
- 2Start with the related worksheet before treating the guide as complete.
- 3Open the linked calculators when a step needs a numeric screen.
- 4Transfer only reviewed values and documented assumptions into project calculations or submittal material.
Worksheet handoff
Calculation tools
Next records
NFPA 72 Battery Sizing Workflow
Open related tools
Before filing
- 1Start from the standard workflow context when the guide controls a design or field-review decision.
- 2Open the related worksheet before treating the guide as complete.
- 3Run the related calculator sequence when a step needs numeric screening.
- 4Retain reviewed inputs, warnings, and handoff notes before final project use.